Half Inch Fans Have Gotta Go
advertisement
The
era of the typical residential fan being rated at .50-in. is coming to a close.
With the increasing pressure drops over today’s cooling coils and filters, it’s
not uncommon to find filter and coil pressures exceeding rated fan pressures…that’s
excluding the pressure drop of the duct system! The result is fans that are delivering
dangerously low airflow, which results in poor system performance and shortened
equipment life.
If
you think the little green emblem on your equipment is an assurance that the
fan has the capacity it should, it’s time to take a closer look. If you’re sure
equipment that is AHRI rated, and matched equipment had “someone” check the fan
capacity to be sure the fan capacity matches the coil pressure drop, check
again.
Nobody’s
got your back on this one. It’s time to take a closer look at some engineering
data and to be sure your system will actually operate as you think it will,
once it’s installed in the field.
Who’s Fault Is It?
The
EPA and DOE don’t seem to understand the problem. Few in committee meetings seem
to care. The prime objectives are Higher
Efficiency Equipment Ratings and don’t upset the apple cart. Everyone at
the top is too busy keeping their plates spinning and their programs funded to
slow down and see what’s actually happening in the field. The focus is on the refrigerant
cycle being the end-all to verification, not actual system operating
efficiency. So when it gets down to it, systems installed in the field are not
saving energy or keeping consumers comfortable, and its up to us to change
that.
We
design and install the systems, so we’re going to have to provide our own
solutions for the problem. The buck stops here. We’re on our own.
What Actually has Happened?
When
a job begins, a typical contractor simply chooses the equipment based on the
highest equipment efficiency matchups assuming the manufacturers or distributors
checked to make sure this equipment would actually function together when installed
in the field.
At
the same time, the manufacturers believe that we follow industry design
practices and will be sure to design and install humongous duct systems to
compensate for their undersized fans. ACCA manual D even states that “the duct
system is to be sized to match the blower that comes with the equipment.”
Oops!
A little assumption here and a little assumption there and the system is a mess.
There’s no way the typical system can possibly function as claimed in the
manufacturer’s specifications or as the contractor promised their customers in
the field.
Real Numbers
Here’s
a scenario that will bring this situation into focus.
There’s
a 95 AFUE furnace coupled with a 19 SEER coil and condensing unit. The fan is
rated for .50-in. total external static pressure; it says so on the equipment
nameplate.
In
essence, the manufacturer is saying: “Here’s
some amazingly efficient equipment. However, right here on the nameplate, as we
individually tested these components, we left a little note that warns, if the
pressure drop of the coil, the filter, the plenums, the ducts, the fittings,
the dampers, grilles and registers exceeds .50-in. this system isn’t going to work.”
However,
if we look at the coil rated with this system, the wet pressure drop at the
rated system airflow is .41-in. Add to that the manufacturer’s top quality high
efficiency super duper air filter system rated a pressure drop of .32-in. and
the total external static pressure of this equipment when installed in the
field will be .73-in. This is almost 50% in excess of the rated fan pressure.
Then
add it to a typical residential duct system with a national average pressure
drop of .32-in. and this system will be operating in the field at 1.03-in. of
total external static pressure. Exceeding the manufacturer’s specifications by
200%!
This
system, although qualifying for the maximum in state and federal energy and tax
incentives, will operate far below the manufacture’s listed efficiency and well
below the assurance of energy efficiency implied by the government assurance
expressed by the incentive program to their citizens.
Who
suffers? The consumer. And they’ll unknowingly suffer for the next 20-years
unless some savvy service tech measures system performance and diagnoses the
problem. Few verification programs will identify the problem. Get the picture?
See Why .50-in. Fans Gotta
Go?
As
years passed and the push continued for higher efficiency equipment, and better
filtration, the scales tipped and nobody caught it. Everyone forgot to set a
standard requiring that the fan capacity has to increase to compensate for the
more restrictive coil and filter pressure drops.
Will
manufacturer’s self police this issue? Don’t count on it. Will our regulators
finally take a realistic look at this issue? Don’t bet on it, my friends. Our
best choice is simply to educate each of our customers to the reality of the
situation, so they will eliminate the low bidders that will try to slip in
poorly performing equipment and attempt to compete with us.
How’s
that for self defense?
Quick Test
One
way to get a quick peek at the static pressures in an HVAC system to help you select
the right fan, is to use the following formula:
Add
together the rated pressure of the cooling coil when wet, plus the rated filter pressure drop (check the manufacturer’s
engineering data) plus the estimated
pressure drop of the supply and return duct system. The total of these pressure
drops will tell you the absolute minimum pressure rating of the fan needed to
move adequate airflow through the system.
Here’s
an example:
Wet
coil rated pressure
.31-in.
Filter
rated pressure .15-in.
Supply
Duct Pressure .16-in. (National Average)
Return
Duct Pressure .16-in. (National Average)
Total
.78-in.
Select
a fan for the system that can deliver the required system airflow at a minimum
of .78. So, probably an .80-in. variable speed fan. Then measure the operating
system static pressure when the system is built to verify actual system
performance.
One Last Note
There
will probably always be use for some equipment made for condos without duct
systems or furnaces used for heating only with fans rated at .50-in. But
generally speaking, when selecting a fan for a ducted system with a cooling
coil and a higher efficiency filter, carefully consider a good quality variable
speed fan. When you do the math you’ll find most systems will do best with a
fan rated near .80-in.
Rob “Doc” Falke serves the
industry as president of National
Comfort Institute, a training company with technical and business level
membership organizations. If you're an HVAC contractor or technician interested
an procedure to help redesign a retrofit HVAC system, contact Doc at robf@ncihvac.com or call him at 800-633-7058. Go to NCI’s
website at
nationalcomfortinstitute.com for free
information, articles and downloads.
Want to use this article? Click here for options!
© 2012 Penton Media Inc.









Acceptable Use Policy blog comments powered by Disqus