Breathe Easy with Demand Control Ventilation

Design and implementation can be challenging, but the payoff is high

Article Tools

HVAC system designers and design/build contractors are familiar with the many "pros" of demand control ventilation systems. Such systems:

  • Save energy
  • Reduce overall heating/cooling load
  • Reduce outdoor air volume
  • Can provide operational flexibility
  • Can reduce re-balancing when used with a dedicated outdoor air system
  • Decrease outdoor air handling unit filter maintenance
  • Can document proper indoor air quality performance. However, as always there are "cons" to go along with the pros. For demand control ventilation systems, these include:
  • Increase in initial cost
  • Increase in system complexity
  • Increase in installation time, control mapping, and commissioning
  • Increase in maintenance cost with sensor monitoring and adjustment
  • Can reduce indoor air quality if installed improperly.

American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE) Standard 62.1, Ventilation for Acceptable Indoor Air Quality, is the guide for most demand control ventilation systems. Standard 62.1 is typically the foundation for local building codes, and addresses outdoor air placement into the occupied breathing zone. It also defines standard office, conference room, and classroom ventilation rates, which are predominately driven by occupancy.

Most base building systems do not apply demand-control ventilation. The design engineer will calculate code-compliant outdoor air volumes based on the maximum projected building occupancy. Although this practice will net a system that is compliant with code and comfortable, it typically results in excess ventilation since buildings are rarely filled to capacity. Building owners are often unaware of how such systems affect energy consumption and air-handler maintenance, both of which directly affect their budget.

Therefore, improving energy and operating efficiency should start with the design process. Design teams applying a demand control ventilation strategy must be aware that such systems will typically have a short payback time in humid regions where economizer hours are limited.

Here is an example of the impact humidity has on a design day. Washington DC and Los Angeles’ LAX airport have been chosen to represent peak summer for a humid climate and for a dry climate respectively. Note the coil loading:

Washington DC ≈ 71 Btuh/cfm summer coil load
(93°F EDB/75°F EWB)
LAX Airport ≈ 44 Btuh/cfm summer coil load
(83°F EDB/68°F EWB)

A Washington DC facility will require approximately 63% more energy to condition outdoor air during summer design conditions, due to moisture alone. This does not include fan energy to address the larger latent coil pressure drops, or winter design loads.

Demand control ventilation can also be used to increase the performance of existing systems. For example, small rooftop equipment or heat pump units dehumidify when the compressors are on. When the compressors are off, the unconditioned humid outdoor air passes directly into the space. The units’ performance may be improved by limiting unnecessary outdoor air. This also applies to an existing unit that has insufficient capacity for a renovated space or future addition. By incorporating demand control ventilation, the unit’s diversified loads may allow continued operation without replacement.

Pick the Low-hanging Fruit
The most basic form of demand control ventilation involves documenting where the occupants will be in the building. For instance, are conference room users the same employees walking from zone to zone, or new visitors arriving for meetings? Do occupants leave for lunch or telecommute on a regular basis? Since this data is difficult to collect for a new facility, sensors and other methods can be employed to identify when occupants are in the building. There are several methods to do this, and as usual it’s best to start with the low-hanging fruit.

For small offices, schools or conference facilities where occupied hours can be tracked with confidence, using a simple timer is possible. Overrides are provided for the user in case after-hour facility use is required. Conference facilities, gyms, and auditoriums typically have the most diversity, largest outdoor air loads, and are typically the first to be reviewed for demand control ventilation controls. The impacts to adjacent space should also be reviewed as part of this process, as older schools and office buildings may rely on conference room or auditorium systems to support kitchen hood exhaust air requirements.

For portions of the country using ASHRAE Standard 90.1, Energy Standard for Buildings Except Low-Rise Residential Buildings, as the energy code, lighting systems require an automatic shut-off capability. This can necessitate occupancy sensors for each individual office. If this is the case, it’s important to coordinate with the electrical contractor to acquire a second set of contacts or output from each sensor. Doing so will provide a control signal that identifies when the occupant is not in the room and outdoor air is no longer required for that space.

Typically, a timer will be used to delay the reduction in outdoor air after occupancy or initiate a room purge prior to occupancy. In this scenario, loss of space cooling may result with the reduction of dedicated outdoor air quantities, and may require an override by the room thermostat. This is especially true for perimeter rooms with high solar or plug heat loads.



Want to use this article? Click here for options!
© 2012 Penton Media Inc.

Back to Top

Featured Videos

More featured videos

Contracting Business eNewsletters

Newest From Hvac-Talk

Why HVAC-TALK?

HVAC-TALK.com is a vibrant, active online community that connects HVAC professionals with a focus on the contracting marketplace.

View Forums

Why Join?

    HVAC-TALK gives contractor suppliers readily available access to the largest online discussion forum in the HVAC contracting market.

Register

Comfortech 2011

Comfortech 2010 Attendee Videos

Executive Editor Terry McIver chats with Comfortech attendees on their impressions of the 2010 show.

Watch videos

Follow us on

Marketplace Ads

Browse Back Issues

May 2012

April 2012

March 2012

February 2012

January 2012

December 2011