Distributed Refrigeration: The Next Wave?
Distributed refrigeration divides the loads into matched groups, with compressors located closer to the loads they're cooling.
advertisement
Most supermarket refrigeration systems follow the traditional approach of using centralized parallel racks connected to circuited pipe systems that circulate refrigerant throughout the entire store. These types of systems have been in use for years and have served customers well. However, other approaches are available for customers looking to satisfy specific goals beyond the capabilities of traditional systems. One such approach is the use of distributed systems.
A Different Approach
Traditional centralized parallel rack systems typically have two or more parallel racks in a single location to handle all of the refrigeration requirements for an entire store.
Within the two major groupings of loads in a typical store, there are almost always narrower ranges of temperature requirements beyond those of just medium-temperature and low-temperature. Medium-temperature applications, for instance, usually differ among diary (22F), meat (21F), seafood (20F), and produce (28F). Low-temperature applications also usually include different temperature requirements for ice-cream (-19F), frozen foods (0-5F), and walk-in freezers (-25F). Although the difference between loads within a group may seem relatively minor, the energy needed to meet a temperature requirement of just one degree (the difference between diary and meat, for instance) does add up. In order for a traditional centralized system to perform adequately, it must run the compressors for a given suction group enough to satisfy the lowest temperature requirement. In the example of the medium-temperature group above, that temperature is 20F, even though the other requirements in the group range upward to 28F. The result of this type of arrangement can be one of unneeded compressor capacity and wasted energy consumption. Improvements to traditional rack systems have addressed this problem by dividing the compressors on a rack into different sub-groups in order to better match the various temperature requirements of the circuits they're connected to, but this adds to the complexity of the store's piping.
Diagram shows layouts of traditional and distributed systems.
Distributed systems divide the loads into matched groups, with the compressors systems physically located closer to the loads they are cooling.
Distributed Systems Simplify Field Piping
Instead of a single system that sends refrigerant through the entire store to all the loads in either of two suction groups, the distributed approach divides the loads into a number of smaller systems and places the systems closer to the loads. This simplifies the field piping and reduces energy losses in the system by reducing the length of the piping runs. A typical distributed system store may have five or more units, each one of which is matched to a narrower set of loads. The units can be placed along the rear exterior of the store, or more often set on the roof, directly over the loads to which they are matched. Distributed system units are generally smaller than centralized rack systems (often including built-in condensers on exterior-placed units), therefore some versions of the units can be situated in back rooms or on top of walk-ins or coolers (requiring connection to separate condensers). Distributed systems can operate more efficiently and eliminate the need for an in-store mechanical room or a complete exterior machine house.
Advantages Include Reduced Piping
In a typical distributed system, anywhere from five to eight units — depending on the size of the store — are mounted on the roof. Although by virtue of their design, the units can be located practically anywhere, the greatest benefit usually comes from mounting them directly above the loads to which they are connected. Among the specific advantages of this kind of approach are: less piping (shorter runs and potentially smaller line sizes); less refrigerant; less potential loss from any one given leak; smaller compressors.
Traditional centralized rack systems may have pipe runs of more than 300 ft. from the machine room — usually at the back of the store — to service or produce cases at or near the front of the store. Multiply that amount of pipe a number of times over for different suction and discharge lines in each suction group of a circuited pipe system and you're talking a lot of pipe. By locating distributed units on the roof directly over the loads, the run length is greatly reduced; some as short as the height of the roof to the floor, approximately 30 ft. in most new stores. Besides significantly cutting down on the amount of piping in the store, these shorter runs reduce the amount of refrigerant contained in the piping (and the entire system), and reduce the potential quantity that could be lost from any single leak. Less overall refrigerant in the system means lower first costs for the customer. With the refrigerant that's in the store divided among multiple distributed systems, any leaks that occur result in no more refrigerant loss than the amount that is contained in one system. With traditional systems, a leak could result in a loss of the entire refrigerant charge.
Shorter line runs decrease the amount of area through which unwanted heat gain from the store can occur, and reduce pressure losses in the refrigerant flowing through the pipes. The result is improved energy performance.