Chainarong Prasertthai/iStock / Getty Images Plus
telephone
Photo 264322000 © Niall Wiggan | Dreamstime.com

ECM Motors: The Good, the Bad and the Ugly

Feb. 8, 2017
When a furnace or air handler with an ECM is installed on a good duct, coil, and filtration system with static pressures within proper design parameters, it can perform flawlessly.In marginal systems with higher-than-design static pressures the motor still may be able to maintain airflow close to design.

Electronically Commutated Motors (ECMs) manufactured today are the best they’ve ever been and can provide unprecedented airflow delivery to match the required BTUH of a heating and/or cooling system.

There are, however, some serious downsides associated with the improper application of these motors in new and existing HVAC systems. Let’s take a candid look at the good, bad, and ugly of the application of these great gems of technology.

The Good

When a furnace or air handler with an ECM is installed on a good duct, coil, and filtration system with static pressures within proper design parameters, it

can perform flawlessly. These systems can deliver precise airflow to match two-speed condenser designs and multi-stage gas furnace firing rates to deliver quiet, draft-free comfort in virtually any configuration.

Additional benefits of these brushless DC motors include low electrical consumption when operating within design Total External Static Pressure (TESP). When installed properly, systems with ECMs can improve dehumidification, reduce register noise, save energy, and provide trouble-free operation.

The Bad

In marginal systems with higher-than-design static pressures for example, a 0.5-in. TESP rated furnace with ECM on a 0.8-in. TESP system the motor

still may be able to maintain airflow close to design. The tradeoff is higher velocities often cause a noisy system and some coil blow-off. The extra torque often required to overcome the higher statics results in higher electrical consumption. This reduces actual equipment EER, which means your customer won’t get the savings of the higher efficiency matchup.

The Ugly

Systems with TESPs of 1.0 and higher, which are more typical than many non-performance-based contractors are willing to admit, can eat up to eight times the power they should be using. When this happens, some ECMs will ramp down and drop airflow significantly. Some older ECM motors will overheat and even fail when constantly running in over-amped conditions. Newer models are designed to drop airflow but time will tell on how well they will
hold up.

Other consequences of high static installations include noise at the registers from higher air velocities. In extreme cases, filter media can be sucked out of its rack causing filter bypass. In very extreme cases filter media can be pulled into the fan, chopped up, and blown through the system causing all sorts of damage.

So, what do you measure? The first thing you should do is install test ports on either side of the blower. Once you’ve installed the test ports, use a digital or analog manometer with a static pressure tip to measure pressure at each location.

High velocities and pressures created by ECMs on systems with dirty evaporator coils can also blow moisture off the coil surfaces into the supply ductwork. This can reduce the system’s dehumidification capability and cause numerous moisture-related indoor air quality issues.

The Answer

These issues can be avoided with good pressure and airflow testing, both before and after the equipment is replaced, and on every system you service.

When you measure, you know. When you don’t measure, you’re just guessing that it will turn out OK.

So, what do you measure? The first thing you should do is install test ports on either side of the blower.

Once you’ve installed the test ports, use a digital or analog manometer with a static pressure tip (see diagram) to measure pressure at each location. TESP is calculated by adding the pressures before and after the fan. Other pressure readings will help you diagnose the cause of high statics – but that’s for another article.

Once you know your TESP and your fan speed setting lookup delivered fan airflow on the manufacturer’s fan table. If you’re replacing or servicing equipment with an ECM, and the TESP exceeds rated capacity, be sure to look up the motor amp draw in the manufacturer’s specifications.

Related Article: Diagnosing ECM Motors

Armed with this information you should do two things: First, alert your customer that their system has a high “blood pressure” problem that needs to be addressed. Second, diagnose the cause of the high statics and recommend solutions to bring them down to acceptable levels.

Of course, there is more to this in terms of troubleshooting and solving these issues. The bottom line is that while the ECM is a great motor, as the servicing or installing contractor it’s your responsibility to make sure its application does not cause unintended consequences detrimental to the health and well-being of your customers’ homes and HVAC systems.

About the Author

Dominick Guarino | Chief Executive Officer

Dominick Guarino is CEO of National Comfort Institute (NCI), (www.nationalcomfortinstitute.com), the nation’s premier Performance-Based training,
certification, and membership organization, focused on helping contractors grow and become more profitable. His email is [email protected]. For more info on performance-based contracting, go to WhyPBC.com or call NCI at 800/633-7058.